Zero-Fault Commissioning Engineering Hub

Inverter Communication Protocol & Commissioning Center

Solar EPCs and installers eliminate on-site troubleshooting delays with Summit's pre-loaded multi-protocol BMS firmware. Native dual-isolated CAN 2.0A/B (500 kbps) and RS485 Modbus RTU guarantee seamless plug-and-play handshakes with Tier-1 hybrid inverters.

CAN Baud Rate
500 kbps
RS485 Baud Rate
9600 / 115200
Max Parallel Stack
16 Units (256kWh)
Interface Type
Dual RJ45 8P8C
Interoperability Matrix

Verified Hybrid & Off-Grid Inverter Brands

Real-world certified BMS telemetry including state-of-charge (SoC), individual cell voltages, temperature, and dynamic charge current limits.

Inverter Manufacturer Supported Inverter Series Protocol & Interface Screen Parameter Verification
Deye
CAN / BMS Port (RJ45)
SUN-5K/8K/10K/12K-SG04LP3, SUN-3/5/6K-SG01HP3 Series CAN 2.0B (500 kbps) & RS485 Modbus Lithium Mode: 00 (CAN) ✓ Verified Plug & Play
Growatt
BMS Port (RJ45)
SPF 3000-5000TL HVM, SPH 4000-10000TL3, WIT/WIS Series CAN / RS485 (Baud: 9600 / 115200) Program 05: LI | Program 36: 51 ✓ Verified Plug & Play
Victron Energy
VE.Can / BMS-Can Port
MultiPlus-II 48V, Quattro 48V via Cerbo GX / Venus OS VE.Can (Baud rate: 500 kbps) Profile: CAN-bus BMS (500 kbit/s) ✓ Certified Compatible
Solis
CAN Port (RJ45)
RHI-3P(5-10)K-HVES-5G, S5-EH1P, S6 Series CAN 2.0A (500 kbps) / RS485 Battery Select: User-Def / CAN ✓ Verified Plug & Play
GoodWe
BMS Port (RJ45)
ET Series (5K~10K), ESA, ES G2, Lynx Home CAN 2.0B / RS485 (500 kbps / 9600) SolarGo: Lithium / CAN Profile ✓ Verified Plug & Play
SMA
RJ45 Com-Sync
Sunny Island 4.4M / 6.0H / 8.0H Series CAN Bus Standard (500 kbps) Batt Type: Li-Ion / CAN Open ✓ Verified Plug & Play
Sofar Solar
BMS Port (RJ45)
HYD 3-20KTL-3PH, ME3000SP, ESI Series CAN / RS485 (500 kbps / 9600) Battery Model: Default CAN ✓ Verified Plug & Play
Hardware Interface Specifications

Hardware Communication Architecture & Cabling Standards

Summit battery cabinets feature dual RJ45 ports (CAN / RS485 for inverter uplink, and RS485 Link for inter-cabinet daisy chaining). Standard CAT5e/CAT6 STP shielded cables are recommended.

01

Dual-Bus Architecture

Independent ports isolate high-speed inverter CAN communication from inter-cabinet RS485 daisy-chain telemetry, preventing packet collisions across large multi-cabinet strings.

Uplink: CAN 2.0B / 485 Link: RS485 Daisy Chain
02

EMI Shielding & Cabling

Always deploy standard STP (Shielded Twisted Pair) CAT5e/CAT6 cables. Maintain a minimum 10 cm physical separation from high-current DC power cables to eliminate EMI interference.

Standard: CAT5e / CAT6 STP Min Separation: ≥10 cm
03

Galvanic Isolation & Termination

Built-in 2.5 kV RMS galvanic isolation safeguards communication circuitry against ground potential shifts and industrial surges. Internal 120Ω termination ensures signal integrity.

Isolation: 2.5 kV RMS Termination: 120Ω Built-in
Multi-Cabinet Parallel Scaling

1~16 Unit Parallel BMS DIP Switch Binary Addressing Guide

When scaling Summit battery cabinets in parallel (from 16kWh up to 256kWh), each cabinet's BMS must be configured with a unique hardware binary DIP address. Only Pack 1 (Master) communicates directly with the hybrid inverter; all other packs (Slaves) communicate with the Master via internal RS485 Link.

Parallel Daisy-Chain Topology
1. Master Cabinet (Pack 1)

DIP Switch set to Address 01 (1 0 0 0). Connect the CAN/RS485 cable directly from Pack 1's BMS port to the hybrid inverter's BMS port.

2. Slave Cabinets (Pack 2~16)

DIP Switches set to Addresses 02 through 16 sequentially. Daisy-chain using standard RJ45 patch cables: Pack 1 RS485-OUT → Pack 2 RS485-IN → Pack 3 RS485-IN...

3. Auto-Aggregation & Protection

Pack 1 aggregates total capacity (e.g. 256kWh), sum of charge/discharge currents, and highest/lowest cell voltages, presenting one unified battery bank to the inverter.

Cabinet Unit Binary Code DIP 1 DIP 2 DIP 3 DIP 4 Assigned Address System Role & Connection
Pack 1 (Master) 1 0 0 0 ON OFF OFF OFF 0x01 Master (BMS to Inverter CAN/RS485)
Pack 2 (Slave 1) 0 1 0 0 OFF ON OFF OFF 0x02 Slave (Link to Pack 1 via RS485)
Pack 3 (Slave 2) 1 1 0 0 ON ON OFF OFF 0x03 Slave (Link to Pack 2 via RS485)
Pack 4 (Slave 3) 0 0 1 0 OFF OFF ON OFF 0x04 Slave (Link to Pack 3 via RS485)
Pack 5 (Slave 4) 1 0 1 0 ON OFF ON OFF 0x05 Slave (Link to Pack 4 via RS485)
Pack 6 (Slave 5) 0 1 1 0 OFF ON ON OFF 0x06 Slave (Link to Pack 5 via RS485)
Pack 7 (Slave 6) 1 1 1 0 ON ON ON OFF 0x07 Slave (Link to Pack 6 via RS485)
Pack 8 (Slave 7) 0 0 0 1 OFF OFF OFF ON 0x08 Slave (Link to Pack 7 via RS485)
Pack 9 (Slave 8) 1 0 0 1 ON OFF OFF ON 0x09 Slave (Link to Pack 8 via RS485)
Pack 10 (Slave 9) 0 1 0 1 OFF ON OFF ON 0x10 Slave (Link to Pack 9 via RS485)
Pack 11 (Slave 10) 1 1 0 1 ON ON OFF ON 0x11 Slave (Link to Pack 10 via RS485)
Pack 12 (Slave 11) 0 0 1 1 OFF OFF ON ON 0x12 Slave (Link to Pack 11 via RS485)
Pack 13 (Slave 12) 1 0 1 1 ON OFF ON ON 0x13 Slave (Link to Pack 12 via RS485)
Pack 14 (Slave 13) 0 1 1 1 OFF ON ON ON 0x14 Slave (Link to Pack 13 via RS485)
Pack 15 (Slave 14) 1 1 1 1 ON ON ON ON 0x15 Slave (Link to Pack 14 via RS485)
Pack 16 (Slave 15) 0 0 0 0 OFF OFF OFF OFF 0x16 Slave (Max 256kWh Expanded Array)
On-Site Commissioning SOP

Inverter Touchscreen & App Setup Walkthrough

Select your inverter brand below to view exact screen menu paths, protocol selection values, and parameter validation benchmarks.

Deye / Sunsynk Hybrid Inverter Commissioning

Compatible with SUN-5K/8K/10K/12K-SG04LP3 low-voltage series

CAN Protocol: 00
Step 1: Cable Connection

Connect the standard RJ45 cable from Summit Cabinet CAN port to the Deye inverter's CAN Port.

Step 2: Battery Mode

On Deye touchscreen, press Gear Icon → Battery Setting → Batt Mode. Check the checkbox for Lithium.

Step 3: Protocol Code

In the Lithium Mode input box, enter 00 (Pylontech CAN compatible). Press Enter / Save.

Step 4: Verify Telemetry

Open Li-BMS Page: Verify Pack Voltage (~51.2V), real-time SoC %, charge current limit (150A per cabinet), and 0 fault alarms.